Frequently Asked Questions about Combustible Gas Alarms

Frequently Asked Questions about Combustible Gas Alarms

With the increasing number of hazardous enterprises and safety-conscious units, everyone has a preliminary understanding of flammable gas alarms, and various problems have followed. Now, some simple problems are used. Company's solution
A flammable gas alarm is used to dissipate flammable gases . It can be applied to gas leakage alarms in places where flammable gases are emitted from refineries, oil depots, liquefied gas stations, gas stations, gas stations, spray booths, and home production rooms.
The state has mandatory regulations, and large-scale industrial production industries and places where gas leaks occur in the production areas require the installation of flammable gas alarms and other equipment. The combustible gas alarm adopts a catalytic combustion type sensor and has a service life of about 2 to 3 years, and has high precision and reliability. Regular calibration of the flammable gas alarm allows one to check the product's detection error while also testing the sensitivity and stability of the instrument. Generally, the flammable gas is calibrated before leaving the factory. In order to ensure the sensitivity of the gas alarm, a calibration is performed every six months or one year.
How to check for faults with flammable gas alarms
1. No flammable gas alarm display
Cause analysis: The power supply voltage is abnormal; the meter head is in water; the circuit board is faulty.
Solution: Detect insurance, wiring; clean the board and dry it, and replace the board if necessary.
2, flammable gas alarm concentration indication does not return to zero
Cause analysis: zero drift; the probe shield has residual flammable gas; the alarm probe or meter is aging.
Solution: Calibrate the zero point under clean air; remove the probe cover, clean the probe dust; replace the probe or instrument.
3, the measured concentration shows a large deviation of the value
Analysis of the cause: The sample gas concentration does not meet the requirements at the time of calibration; the sensor range setting is incorrect; the sensor is aging.
Remedy: Recalibrate with qualified sample gas; reset sensor range; replace with new sensor.
Precautions during the use of flammable gas alarms
1. The installation position, installation angle, protective measures and system wiring of the flammable gas alarm should be protected against electromagnetic interference; high temperature, humidity, rain and other environments should be avoided.
2. Select a suitable position according to the density of the combustible gas to install a gas- fired alarm . The gas with a gas density lower than that of the air should be installed at a position about 1 m above the leak point; the gas with a density greater than the air, The probe should be installed below the leak point and approximately 0.5m above the ground; the gas to be measured with a density close to the air should be as close as possible to the leak. For example, where there is a hydrogen leak, the detector should be installed on the plane above the leak.
The flammable gas alarm is equivalent to an automatic fire extinguisher, which can drive the exhaust, cut and spray system to prevent explosion, fire and poisoning accidents, thus ensuring safe production.